EPA 608 Leak-Rate Calculator
Plan repairs faster with a graphical gauge that maps your calculated refrigerant leak rate to EPA’s 10/20/30 percent trigger bands.
EPA Program
Determines regulatory trigger and response window.
Calculation Method
Keep consistent per facility (EPA requirement).
Select the trigger band that applies to this equipment.
Documented full refrigerant capacity at normal operating conditions.
Record pounds added for this service event.
Annualizing uses the smaller of this value or 365 days.
Annualizing formula: lbs added × 365 ÷ days since the last addition.
Colored fill shows your leak rate as a fraction of the scale. Markers indicate EPA triggers (10/20/30%). The diamond marks the trigger that applies to the selected category.
Comfort Cooling, Refrig. Transport, Other
Repair required within 30 days (or 120 days if process shutdown) plus verification testing (40 CFR §82.157).
Purge Exclusion: Purged refrigerant destroyed at ≥98% efficiency does not count toward the annual leak-rate calculation (keep records). § 82.157(k); § 84.106(k).
- 40 CFR §82.157 — Leak repair timelines & triggers (ODS, ≥50 lb)
- 40 CFR §84.106 — Leak repair under AIM Act (HFCs, ≥15 lb)
- Step-by-step guide to EPA leak-rate math ↗
Disclaimer: This tool summarizes federal rules as of Sep 2025 for convenience only. Consult the eCFR links above for controlling text.